Suggestions

Chlorine Dioxide System Bello Zon® CDKd

8 – 12,000 g/h chlorine dioxide. The maximum volume of water that can be treated with metering of 0.2 ppm ClO2, depending on the size of the system: 60,000 m3/h

Chlorine dioxide system for the metering of chlorine dioxide with concentrated starting chemicals. The proven three-stage safety concept protects people and the environment. The certified output guarantees efficient chlorine dioxide production. Bello Zon® CDKd can be easily and safely integrated into any water treatment process.

Product description

Chlorine dioxide system Bello Zon® CDKd treats medium to large volumes of water with concentrated chemicals.

There is an intrinsically safe pre-dilution station for concentrated hydrochloric acid integrated in this chlorine dioxide Chlorine dioxide is an exceptionally reactive gas, which is not stored due to its instability ... more in the glossary system. The consumption of hydrochloric acid can therefore be automatically adapted on site to the individual operating conditions by means of a patented process. Savings of up to 20 %.

The system control offers impressive and user-friendly menu navigation and ensures the precise production of chlorine dioxide Chlorine dioxide is an exceptionally reactive gas, which is not stored due to its instability ... more in the glossary. The chemicals are mixed perfectly in a reactor made of food-safe PVDF. You thereby benefit from maximum output with the lowest possible consumption of chemicals and maximum operating safety. The requirements set by the Industry 4.0 standards of tomorrow are met thanks to communication via popular bus systems, a web server A web server is a software application executed by the DULCOMARIN® II. more in the glossary and our DULCONNEX Platform.

The construction and operating mode of the system also complies with all requirements of DVGW specifications W 224 and W 624 and the system is intended for operation with concentrated chemicals Bello Zon® chlorite (24.5% NaClO2) and acid (25 – 37% HCl). The liquid levels of the starting chemicals can either be displayed and monitored by external liquid level sensors or by adaptive liquid level monitoring for which a patent has been applied.

Your benefits

  • Cost savings through optimised acid consumption
  • Communication interfaces via bus systems or DULCONNEX
  • System does not stop due to empty starting feed chemical tanks thanks to precise level indicators
  • Consumption levels can be planned, enhanced availability and economical operation thanks to verification of chlorine dioxide metering and system output
  • Simple compliance with documentation obligations and evidence of correct operation using automatically generated reports and alarms
  • Remote maintenance thanks to DULCONNEX in a safe environment, yet still on-site. For more information:https://dulconnex.prominent.com/welcome.html

Field of application

  • Municipal drinking water and waste water treatment
  • Industrial process and cooling water
    1 2 3 4 5 6 7

    Technical Details

    Power supply

    • 100-230 V, 50/60 Hz

    Inputs

    • 4 analogue inputs (0/4-20 mA)
      • Water flow
      • Control variable
      • Acid level
      • Chlorite level
    • 4 digital inputs
      • Contact water meter 0.25-20 Hz
      • Pause
      • Alternative metering
      • External fault

    Outputs

    • 1 operating signal relay
    • 1 alarm signal relay
    • 1 warning signal relay
    • Mains output for control of the bypass pump
    • 2 freely configurable analogue outputs (0/4-20 mA)

    Operating substances

    • 24.5% sodium chlorite, purity according to EN 938
    • 25-37 % hydrochloric acid, purity according to EN 939
    • Particle-free water

    Degree of protection

    • IP 65

    Bus communication options

    • Modbus TCP / DULCONNEX
    • Modbus RTU / DULCONNEX
    • Profibus DULCONNEX
    • Profinet DULCONNEX

    Technical Data

    Type

    Chlorine dioxide metering rate (min.…max./hour, min./day)*

    Max. operating pressure**

    Operating temperature

    Chlorite

    Dimensions of the bypass connector

    g/h

    g/d

    bar

    °C

    DN

    * The metering figures relate to 5 or 2 bar back pressure and an ambient temperature of 20 °C.
    The minimum capacity per hour is based on the fact that when the system is operating at below
    5 % of the nominal capacity, continuous metering is no longer possible as the pumping frequency of the
    metering pumps is then low. When plants are not operating continuously, the reactor contents
    should be changed at least twice a day. Therefore do not operate the system below the stated
    minimum capacity/day.

    ** at an ambient temperature of 35 °C

    CDKd 150

    7.5…150

    56

    8

    10…40

    8x5

    6x4

    25

    CDKd 400

    20…400

    140

    8

    10…40

    12x9

    8x5

    25

    CDKd 900

    45…900

    300

    8

    10…40

    Pressure hose nozzle d16

    8x5

    25

    CDKd 2000

    100…2,000

    700

    5

    10…40

    Pressure hose nozzle d20

    12x9

    40

    CDKd 2800

    140…2,800

    700

    5

    15…40

    Pressure hose nozzle

    12x9

    40

    CDKd 7300

    370…7,300

    1,750

    3

    15…40

    Pressure hose nozzle

    Pressure hose nozzle d16

    40

    CDKd 12000

    600…12,000

    1,750

    2

    18…40

    Pressure hose nozzle d32

    Pressure hose nozzle d16

    40

    Type

    Dimensions H x W x D (approx.)*

    Weight

    Supply voltage 230 V**

    Supply voltage 115 V**

    Power consumption without bypass pump

    Power consumption with bypass pump

    HCl***

    NaClO2***

    mm

    kg

    A

    A

    W

    W

    l/h

    l/h

    * including main system, pre-dilution and rinse valve, without bypass pump and water feed section

    ** 230 V figures with bypass pump (CDKd 150-900), 115 V figures without bypass pump

    *** Sodium chlorite (NaClO2) 24.5 %, purity in accordance with EN 938, hydrochloric acid 25-36%, purity in accordance with EN 939. The chemical consumption may vary depending on the temperature. The hydrochloric acid consumption is calculated for a concentration of 30%. Up to 25% hydrochloric acid can be saved with the aid of automatic acid adjustment.

    CDKd 150

    1,300 x 1,000 x 250

    89

    3.9

    1.7

    110

    640

    0.9

    0.9

    CDKd 400

    1,675 x 900 x 460

    119

    3.9

    1.8

    160

    690

    2.5

    2.5

    CDKd 900

    1,920 x 920 x 520

    131

    4.2

    2.3

    210

    740

    5.6

    5.6

    CDKd 2000

    1,880 x 1,320 x 570

    201

    -

    3.7

    370

    -

    12.3

    12.3

    CDKd 2800

    1,880 x 1,320 x 570

    201

    -

    3.7

    370

    -

    17.3

    17.3

    CDKd 7300

    2,250 x 1,850 x 500

    216

    -

    8.6

    610

    -

    45.1

    45.1

    CDKd 12000

    2,250 x 1,850 x 500

    216

    -

    8.6

    610

    -

    74.1

    74.1

    Ambient conditions:

    Permissible relative air humidity (non-condensing)max. 85% rel.
    Permissible ambient temperature40 °C
    Permissible temperature of chemicals10 … 35 °C
    Storage and transport temperature-10 … +40 °C
    Degree of protectionIP 65

    Downloads for Chlorine Dioxide System Bello Zon® CDKd

    More in the Download Centre

    0 Results
    Filter by document type
    Application Example / Reference (0)
    Brochure / Flyer (0)
    Catalogue (0)
    Certificate / Declaration (0)
    Data Sheet (0)
    Drawing / Dimensional Drawing / 3D (0)
    Exploded View / Spare Parts (0)
    Material Safety Data Sheet (0)
    Operating Instructions (0)
    Others (0)
    Press Release (0)
    Publication / Article (0)
    Software (0)
    Wiring Diagram (0)

    Selected filters:

    Matching downloads

    Sort by A to Z
    Load more matches ...
    No more matches available!

    Unfortunately, we did not find an appropriate match.

    All words written correctly?
    Search again with fewer or different search terms?

    Please try again later

    Service Unavailable

    The server is temporarily unable to service your request due to maintenance downtime or capacity problems. Please try again later.

    Overview

    Chlorine dioxide system Bello Zon® CDKd treats medium to large volumes of water with concentrated chemicals.

    There is an intrinsically safe pre-dilution station for concentrated hydrochloric acid integrated in this chlorine dioxide Chlorine dioxide is an exceptionally reactive gas, which is not stored due to its instability ... more in the glossary system. The consumption of hydrochloric acid can therefore be automatically adapted on site to the individual operating conditions by means of a patented process. Savings of up to 20 %.

    The system control offers impressive and user-friendly menu navigation and ensures the precise production of chlorine dioxide Chlorine dioxide is an exceptionally reactive gas, which is not stored due to its instability ... more in the glossary. The chemicals are mixed perfectly in a reactor made of food-safe PVDF. You thereby benefit from maximum output with the lowest possible consumption of chemicals and maximum operating safety. The requirements set by the Industry 4.0 standards of tomorrow are met thanks to communication via popular bus systems, a web server A web server is a software application executed by the DULCOMARIN® II. more in the glossary and our DULCONNEX Platform.

    The construction and operating mode of the system also complies with all requirements of DVGW specifications W 224 and W 624 and the system is intended for operation with concentrated chemicals Bello Zon® chlorite (24.5% NaClO2) and acid (25 – 37% HCl). The liquid levels of the starting chemicals can either be displayed and monitored by external liquid level sensors or by adaptive liquid level monitoring for which a patent has been applied.

    Your benefits

    • Cost savings through optimised acid consumption
    • Communication interfaces via bus systems or DULCONNEX
    • System does not stop due to empty starting feed chemical tanks thanks to precise level indicators
    • Consumption levels can be planned, enhanced availability and economical operation thanks to verification of chlorine dioxide metering and system output
    • Simple compliance with documentation obligations and evidence of correct operation using automatically generated reports and alarms
    • Remote maintenance thanks to DULCONNEX in a safe environment, yet still on-site. For more information:https://dulconnex.prominent.com/welcome.html

    Application

    Technical Data

    Downloads

    Contact us

    Wesley Sutton

    Managing Director, ProMinent Fluid Controls UK Ltd.

    »We are always available to help. Don't hesitate to contact us.«

    +44 1530 560 555  Send request   

    Matching Products

    1 2

    ProMinent Newsletter - receive latest news, customized for you! subscribe now