Measurand
|
Measuring and Control Range |
Resolution |
Sensor input |
| pH |
0 - 14 |
0,01pH |
Input resistance > 1012 W
Clamp standard signal 0/4...20 mA |
| Redox |
-1000 - +1000 mV |
1 mV |
Input resistance > 5 x 10 11 W
Clamp standard signal 0/4...20 mA
|
| Chlorine |
0,005 - 0,500 ppm
0,05 - 2,00 ppm
0,05 - 5,00 ppm
0,05 - 10,00 ppm
0,05 - 20,00 ppm
0,05 - 50,00 ppm
0,05 - 100,00 ppm
|
0,001 ppm
0,01 ppm |
Clamp standard signal 0/4...20 mA
|
| Bromine |
0,02 - 2,00 ppm
0,1 - 10,0 ppm |
0,01 ppm |
Clamp standard signal 0/4...20 mA |
| Conductive conductivity |
0 - 20 µS/cm
0 - 200 µS/cm
0 - 2 mS/cm
0 - 200 mS/cm |
0,001 µS/cm |
Clamp conductive conductivity |
| Inductive conductivity |
0 - 200 µS/cm
0 - 2 mS/cm
0 - 200 mS/cm
0 - 2000 mS/cm
|
0,01 µS/cm |
Clamp inductive conductivity |
| Chlorine dioxide |
0,005 - 0,500 ppm
0,05 - 2,00 ppm
0,05 - 10,00 ppm
0,05 - 20,00 ppm
|
0,001 ppm 0,01 ppm |
Clamp standard signal 0/4...20 mA |
| Chlorite |
0,005 - 0,500 ppm
0,05 - 2,00 ppm
|
0,001 ppm 0,01 pmm |
Clamp standard signal 0/4...20 mA |
| Ozone |
0,05 - 2 ppm |
0,01 ppm |
Clamp standard signal 0/4...20 mA |
| Fluoride |
0,05 - 10 mg/l |
0,01 ppm |
Clamp standard signal 0/4...20 mA |
|
Hydrogen peroxide
|
1 - 20 ppm
20 - 200 ppm
20 - 2000 ppm
|
0,01 ppm |
Clamp standard signal 0/4...20 mA |
| Peracetic acid |
1 - 20 ppm
20 - 200 ppm
20 - 2000 ppm
|
0,01 ppm |
Clamp standard signal 0/4...20 mA |
| Temperature |
0 - 100 °C
|
0,1 °C |
Clamp Pt 100 / Pt 1000
Clamp standard signal 0/4...20 mA
|
| Analogue signal |
0/4...20 mA |
|
Clamp standard signal 0/4...20 mA |